| ZENITH ZBTSD
BYPASS ISOLATION DELAYED TRANSITION SERIES AUTOMATIC TRANSFER
SWITCH |
|
Description
The ZBTSD Series
incorporates the features of the ZBTS Bypass-Isolation Switch
with those of the ZTSD unit for transfer of large motor loads,
transformers, uninterruptible power supplies (UPS) systems or
load shedding to a neutral "off" position.
In critical systems
such as those of hospitals and airports, power cannot be
interrupted for maintenance and testing of automatic transfer
switches (ATSs).
In such circumstances,
a bypass-isolation switch is essential and often required by
code. The GE Zenith Controls ZBTSD Series Delayed Transition
Transfer/Bypass-Isolation Switch meets requirements for
inspection and/or maintenance of the delayed transition
transfer switch without power interruption.
The ZBTSD Series
incorporates the rugged construction of all our ZTS Series
switches with a quick-make/quick-break manual load transfer
handle and our control/interlock system, consisting of both
mechanical and electrical interlocks.
The bypass uses normal
failure sensing and a time delay to start the engine
automatically if a failure occurs when the ATS has been
removed for service.
Contact Nikki or David for
information and pricing
Toll Free
888.861.8984
Ph:
605.341.6160
Fax:
605.341.9791
nikki@genpropower.com
davidp@genpropower.com
Taxes collected for South Dakota, Wyoming, and Nebraska |
Features and Benefits
 |
Load is not
interrupted during bypass operation
|
 |
High close-in and
withstand capability
|
 |
Temperature rise
test per UL 1008 conducted after overload and endurance
tests in unventilated enclosure - exceeds UL requirements
|
 |
Available in ZBTS
(utility-generator), ZBTSU (utility-utility), ZBTSG
(generator-generator) and ZBTSM (manual) configurations;
models include standard, delayed and closed transition
|
 |
Transfer switch is
located on a draw-out mechanism to facilitate maintenance
|
 |
Emergency power
systems can be electrically tested without disturbing the
load
|
 |
Power cables do not
have to be disconnected to remove transfer switch
|
 |
Bypass to any
available source with transfer switch removed
|
 |
Engine start
circuit maintained during bypass operation; normal power
failure causes engine start contact closure even with the
ATS removed
|
 |
Diagnostic lights
and detailed instructions for simple step-by-step
operation
|
 |
Mechanical and
electrical interlocks ensure proper sequence of operation
|
 |
Bypass switch
contacts are closed only during the bypass-isolation
operation
|
 |
Silverplated copper
bus interconnection of the transfer and bypass switches on
all sizes
|
Product Scope
 |
Ratings 100 to 4000
amperes
|
 |
2, 3 or 4 poles
|
 |
Open type, NEMA 1,
3R, 4, 4X and 12
|
 |
Available with ZTS,
ZTSD and ZTSCT Series Transfer Switch
|
 |
Bypass and transfer
switch have identical ratings
|
 |
Suitable for
emergency and standby applications on all classes of load,
100% tungsten rated through 400 amps
|
 |
UL 1008 listed at
480 VAC
|
 |
CSA C22.2 No. 178
certified at 600 VAC
|
 |
IEC 947-6-1 listed
at 480 VAC
|
• ASCO PARTS • ASCO 165 SERIES • ASCO 300 SERIES • ASCO 7000 BYPASS ISOLATION • ASCO 7000 SERIES • ASCO 7000 CLOSED TRANSITION • ASCO 7000 DELAYED TRANSITION • ASCO 7000 Series • ZENITH ZBTS BYPASS • ZBTSCT Closed Transition • ZBTSD ZENITH • ZENITH ZTS SWITCH • ZTSCT ZENITH • ZENITH ZTG SWITCH • ZENITH ZTGD • ZTGSE ZENITH • ZTSD ZENITH • ZENITH ZTX SERIES • |
|

|