ZENITH ZBTSCT CLOSED TRANSITION BYPASS ISOLATION SERIES AUTOMATIC TRANSFER SWITCH

Description

The ZBTSCT Closed Transition Transfer Switch may be outfitted with a bypass-isolation switch for the utmost in reliability and versatility. The ZBTSCT Series provides the ability to withdraw the transfer switch unit for maintenance or inspection. 

Using the proven switching technology of the ZTS/ZTSD Series of transfer switches, combined with controls developed during GE Zenith Controls' years of experience, the ZBTSCT Series allows an overlap of normal and alternate sources of less than 100 milliseconds.

When conditions are sensitive to generator voltage drop or frequency dips, GE Zenith Controls can provide a variation of the closed transition method of transfer that combines the attributes of a ZTSCT with generator paralleling switchgear. This method of transfer requires greater coordination with the utility company and, typically, more sophisticated relay protection schemes. We suggest you specify option SL on your ZBTSCT (SL) unit and consult your GE Zenith Controls representative early in the project cycle to ensure proper application.

(Download Brochure)     

Features and Benefits

bullet
Incorporates the applicable features of the ZTS and ZBTS Series 
bullet
Source parallel time of less than 100 milliseconds 
bullet
Closed transition operation (no power interruption) during transfer and retransfer when sources are within specified parameters 
bullet
Open transition transfer operation is initiated upon a source failure 
bullet
1Available in ZTSCT (utility-generator), ZTSCTU (utility-utility), ZTSCTM (manual) configurations 
bullet
Transfer switch is located on a draw-out mechanism to facilitate maintenance 
bullet
Emergency power systems can be electrically tested without disturbing the load 
bullet
Power cables do not have to be disconnected to remove transfer switch 
bullet
Bypass to any available source with transfer switch removed 
bullet
Engine start circuit maintained during bypass operation; normal power failure causes engine start contact closure even with the ATS removed 
bullet
nDiagnostic lights and detailed instructions for simple step-by-step operation 
bullet
Mechanical and electrical interlocks ensure proper sequence of operation 
bullet
nBypass switch contacts are closed only during the bypass-isolation operation 
bullet
Silverplated copper bus interconnection of the transfer and bypass switches on all sizes 

Product Scope

bullet
Ratings 100 to 4000 amperes 
bullet
2, 3 or 4 poles 
bullet
Open type, NEMA 1, 3R, 4, 4X and 12 
bullet
Available in Transfer Switch (ZTSCT) or ZBTSCT (transfer/bypass switch) styles
bullet
Suitable for emergency and standby applications on all classes of load, 100% tungsten rated through 400 amps 
bullet
kUL 1008 listed at 480 VAC 
bullet
CSA certified at 600 VAC 
bullet
IEC listed 480 VAC