3-second time delay to override momentary utility source.
15-second transfer to emergency time delay to allow engine
generator to stabilize after starting.
15-second time delay after transfer to the standby source to
ignore momentary voltage dips on the generator during initial
loading.
5-minute time delay on retransfer to allow utility source to
stabilize prior to transferring the load back to utility.
1-minute unloading running time delay for engine generator
cool-down before shutdown
Diagnostic Indicators
The 165 Automatic Transfer Switch has a unique built-in automatic
digital diagnostic monitoring system, which provides status on
potential system problems such as: generator failed to start;
generator over frequency; transfer switch did not transfer; and
more. It's one more way you can count on ASCO to provide continuous
power protection ...anytime